omdl  v0.9.5
OpenSCAD Mechanical Design Library

[utility_pipe] Electrical metalic conduit; emt; thin wall. More...

+ Collaboration diagram for emt:

Files

file  utility_pipe_emt.scad
 [utility_pipe] Electrical metalic conduit; emt; thin wall.
 

Variables

 dtc_structural_utility_pipe_emt
 
 dtr_structural_utility_pipe_emt
 

Detailed Description

[utility_pipe] Electrical metalic conduit; emt; thin wall.

Requires:
include <omdl-base.scad>;
include <database/component/structural/utility_pipe_emt.scad>;
parameters

Electrical metalic conduit table

idxnominal size (ns)nominal size (ns_mm)outside diameter (od_in)outside diameter (od_mm)internal diameter (id_in)internal diameter (id_mm)
03/8100.5770.578740.4930.492126
11/2160.7060.7047240.6220.622047
23/4210.9920.921260.8240.822835
31271.1631.161421.0491.04724
41-1/4351.511.511811.381.38189
51-1/2411.741.740161.611.61024
62532.1972.196852.0672.06693
72-1/2632.8752.874022.7312.73228
83783.53.53.3563.35433
93-1/291443.8343.83465
1041034.54.54.3344.33465
Note
The measurements in the table above are shown with: length_unit_base="in". These measurements will convert when the base units are changed. See Length Units for more information on setting the base units.
References:
emt
thin wall

Variable Documentation

◆ dtc_structural_utility_pipe_emt

dtc_structural_utility_pipe_emt

<map> emt structural data table columns map.

Definition at line 281 of file utility_pipe_emt.scad.